Universal Data Manager
Technical Data
61
Hysteresis
Can be configured for limit values in the setup
Long-term drift
To IEC 61298-2: max. ±0.1%/year (of measuring range)
15.6 Installation
Mounting location and
installation dimensions
The device is designed for use in a panel in non-hazardous areas.
144 (5.67)
144 (5.67)
141 (5.55)
17 (0.67)
34
(1.34)
X
Y
A0019301
11
Panel mounting and dimensions in mm (in)
Please observe the installation depth of approx. 158 mm (6.22 in) for the device incl.
terminals and fastening clips.
• Panel cutout: 138 to 139 mm (5.43 to 5.47 in) x 138 to 139 mm (5.43 to 5.47 in)
• Panel strength: 2 to 40 mm (0.08 to 1.58 in)
• Angle of vision: from the midpoint axis of the display, 75° to the left and right, 65° above
and below.
• A minimum distance of 15 mm (0.59 in) mm (inch) between the devices must be
observed if aligning the devices in the Y-direction (vertically above one another). A
minimum distance of 10 mm (0.39 in) mm (inch) between the devices must be observed
if aligning the devices in the X-direction (horizontally beside one another).
• Securing to DIN 43 834