Universal Data Manager
Commissioning
33
To configure the device via a web server, you must have Administrator or Service
access. Prior to accessing the web server, create an ID and password in the main menu
under
"Setup -> Advanced setup -> Communication -> Ethernet -> Configuration
Web server -> Authentification"
.
ID default value: admin; Password: admin
Note: The password should be changed during commissioning!
Establishing a connecting and setup
Procedure for setting up a connection:
1. Connect the device to the PC via Ethernet
2. Start the browser at the PC; open the web server for the device by entering the IP
address: http://<ip-adresse> Note: Leading zeros in IP addresses must not be entered
(e.g. enter 192.168.1.11 instead of 192.168.001.011).
3. Enter ID and password, and confirm each by clicking "OK"
4. The web server shows the momentary value display of the device. Click "Menu" in the
web server taskbar.
5. Starting configuration
Continue with device configuration in accordance with the Operating Instructions for the
device. The complete Setup menu i.e. all of the parameters listed in the Operating
Instructions, can also be found on the web server. Once configuration is complete, log out
of the web server.
NOTICE
Undefined switching of outputs and relays
‣
During configuration using a web server, the device may assume undefined statuses!
This may result in the undefined switching of outputs and relays.
Procedure to establish a direct connection via Ethernet (point to point connection):
(→ 36)
9.4.4
Setup via configuration software (included in scope of supply)
To configure the device using the configuration software, connect the device to your PC via
USB or Ethernet.
Establishing a connection and setup
For details, see the Operating Instructions on the configuration software DVD
provided
Continue with device configuration in accordance with the Operating Instructions for the
device. The complete Setup menu, i.e. all the parameters listed in the Operating
Instructions, can also be found in the configuration software.
NOTICE
Undefined switching of outputs and relays
‣
During configuration using the configuration software, the device may assume
undefined statuses! This may result in the undefined switching of outputs and relays.
9.5
Advanced settings (Expert menu)
You can access the main menu by pressing the Navigator during operation. Turn the
Navigator to navigate to the
"Expert"
menu. Press the Navigator to open the menu.