Universal Data Manager
Anhang
131
Navigation
Expert → Application → Limits → Set point x → Event text LV on
Direct access code: 450009-0xx
Examples: Set point 1: 450009-000; Set point 30: 450009-029
Description
This text (including date and time) is shown on the display and/or stored in the event log.
Only available if "LV messages" is set to "Acknowledge" or "Save message" is set to "Yes".
If no text is entered, the device generates its own text (e.g. Analog 1 > 100%).
User entry
Text (max. 22 characters)
Event text LV off
Navigation
Expert → Application → Limits → Set point x → Event text LV off
Direct access code: 450010-0xx
Examples: Set point 1: 450010-000; Set point 30: 450010-029
Description
The same as "Event text LV on", but on return from alarm to normal condition.
User entry
Text (max. 22 characters)
Record duration of LV on
Navigation
Expert → Application → Limits → Set point x → Record duration of LV on
Direct access code: 450011-0xx
Examples: Set point 1: 450011-000; Set point 30: 450011-029
Description
The duration of a set point violation can be recorded. The duration is appended to the
"limit value off" event text (format: <hhhh>h<mm>:<ss>).
Power outage times do not affect the duration. If the set point was violated before the
power off and is still violated after the power off, the duration continues.
Options
No, Yes
Factory setting
No
Save cycle
Navigation
Expert → Application → Limits → Set point x → Save cycle
Direct access code: 450012-0xx
Examples: Set point 1: 450012-000; Set point 30: 450012-029
Description
Normal: Save in normal store cycle.
Alarm cycle: Fast storage during an alarm violation, e.g. every second. Attention: Requires
higher memory capacity.
• The save cycle is set under signal groups (→ 133).
• In the event of an alarm violation, all the groups are saved in the alarm cycle.