ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
58
Technical Data
Universal Data Manager
58
Relay
Digital
in
Analog
in
Ethernet RS232/RS485
USB
Auxiliary
voltage output
RS232/RS485 2 kV
DC
500 V
DC
500 V
DC
500 V
DC
-
500 V
DC
500 V
DC
USB
2 kV
DC
500 V
DC
500 V
DC
500 V
DC
500 V
DC
Galvanically
connected
500 V
DC
Auxiliary
voltage output
2 kV
DC
500 V
DC
500 V
DC
500 V
DC
500 V
DC
500 V
DC
-
Relay outputs
A mix of low voltage (230 V) and safety extra low voltage (SELV circuits) is not permitted
at the connections of the relay contacts.
Alarm relay
1 alarm relay with changeover contact.
Standard relay
5 relays with NO contact, e.g. for limit value messages (can be configured as NC contact).
Relay switching capacity
• Max. switching capacity: 3 A@ 30 V DC
• Max. switching capacity: 3 A@ 250 V AC
• Min. switching load: 300 mW
Switching cycles
>10
5
Cable specification
Cable specification, spring terminals
All connections to the rear of the unit are designed as screw or spring terminal blocks with
reverse polarity protection. This makes the connection very quick and easy. The spring
terminals are unlocked with a slotted screwdriver (size 0).
Please note the following when connecting:
• Wire cross-section, auxiliary voltage output, digital I/O and analog I/O: max. 1.5 mm
2
(14 AWG) (spring terminals)
• Wire cross-section, power supply: max. 2.5 mm
2
(13 AWG) (screw terminals)
• Wire cross-section, relays: max. 2.5 mm
2
(13 AWG) (spring terminals)
• Stripping length: 10 mm (0.39 in)
No ferrules have to be used when connecting flexible wires to spring terminals.
Cable type
Use shielded signal lines for interfaces!