Description
Cable open circuit detection
Only visible if signal = voltage and range = 1-5V or 1-5V squared.
Options
Off, On
Factory setting
On
Lower error value
Navigation
Expert → Inputs → Universal inputs → Universal input x → Fault mode → Lower error
value
Direct access code: 220065-0xx
Examples: Universal input 1: 220065-000; Universal input 12: 220065-011
Description
When NE 43 is switched off, defines the value that must be undershot for the device to
output an error.
Only visible if signal = current, range = 4 to 20mA and NAMUR NE 43 = off
User entry
Number (max. 8 digits); 0 to 4
Factory setting
3.9
Upper error value
Navigation
Expert → Inputs → Universal inputs → Universal input x → Fault mode → Upper error
value
Direct access code: 220066-0xx
Examples: Universal input 1: 220066-000; Universal input 12: 220066-011
Description
When NE 43 is switched off, defines the value that must be exceeded for the device to
output an error.
Only visible if signal = current, range = 4 to 20mA and NAMUR NE 43 = off
User entry
Number (max. 8 digits); 20 to 22
Factory setting
20.8
On error
Navigation
Expert → Inputs → Universal inputs → Universal input x → Fault mode → On error
Direct access code: 220061-0xx
Examples: Universal input 1: 220061-000; Universal input 12: 220061-011