ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
84
Anhang
Universal Data Manager
84
16.1.2 "Inputs" submenu
Settings for the analog and digital inputs.
Submenu "Universal inputs -> Universal input x"
Navigation
Expert → System → Universal inputs→ Universal input x
Description
Settings for the connected measuring points. View or change settings for the selected
channel.
x = place holder for selected universal input
Signal
Navigation
Expert → Inputs → Universal inputs → Universal input x → Signal
Direct access code: 220000-0xx
Examples: Universal input 1: 220000-000; Universal input 12: 220000-011
Description
Select the type of signal connected (current, voltage, etc.). The channel is switched off if no
signal type is selected (factory default).
Options
Switched off, Current, Voltage, Resistance temperature detector, Thermocouple, Pulse
counter, Frequency input, Modbus Slave (option)
Factory setting
Switched off
Range
Navigation
Expert → Inputs → Universal inputs → Universal input x → Range
Direct access code: 220001-0xx
Examples: Universal input 1: 220001-000; Universal input 12: 220001-011
Description
Select the input range or which resistance thermometer/thermocouple is connected. The
respective terminal layout can be found in the operating manual or on the rear of the unit.
Only visible if signal ≠ switched off
Options
Switched off, 4-20 mA, 0-20 mA, 0-5 mA, 0-20 mA squared, 4-20 mA squared, ±20 mA,
0-1 V, 0-10 V, 0-5 V, 1-5 V, ±150 mV, ±1 V, ±10 V, ±30 V, 0-1 V squared, 0-10 V
squared, 1-5 V squared, Pt100 (IEC), Pt100 (JIS), Pt100 (GOST), Pt500 (IEC), Pt500 (JIS),
Pt1000 (IEC), Pt1000 (JIS), Pt46 (GOST),Pt50 (GOST),Cu50 (GOST, a=4260),Cu50 (GOST,
a=4280), Cu53 (GOST, a=4280), Cu100 (GOST, a=4280), Type A (W5Re-W20Re), Type B
(Pt30Rh-Pt6Rh), Type C (W5Re-W25Re), Type D (W3Re-W25Re), Type J (Fe-CuNi), Type
K (NiCr-Ni), Type L (Fe-CuNi), Type L (Fe-CuNi, GOST), Type N (NiCrSi-NiSi), Type R
(Pt13Rh-Pt), Type S (Pt10Rh-Pt), Type T (Cu-CuNi), Frequency input, Modbus
Factory setting
Switched off