Universal Data Manager
Operation options
25
Item
No.
Operating function (display mode = display of measured values)
(Setup mode = operating in the Setup menu)
9
In Display mode: current group name, type of evaluation
'
In Setup mode: name of the current operating item (dialog title)
10
In Display mode: displays current date/time
In Setup mode: --
11
In Display mode: alternating display indicating the percentage space on the SD card or USB stick that
has already been used.
Status symbols are also displayed in alternation with the memory information (see the following
table).
'
In Setup mode: the current "direct access" operating code is displayed
12
In Display mode: display of current measured values and the status in the event of an error/alarm
condition. In the case of counters, the type of counter is displayed as a symbol (see the following
table).
If a measuring point has limit value status, the corresponding channel identifier is highlighted
in red (quick detection of limit value violations). During a limit value violation and device
operation, the acquisition of measured values continues uninterrupted.
7.3.1
Display representation of symbols used in operation
Item
No.
Function
Description
8,12
Symbols for counters:
å
0 /
å
1
Interim analysis/ external analysis
å
D
Daily analysis
å
M
Monthly analysis
å
Y
Annual analysis
å
Totalizer
8, 12
Channel-related symbols:
Violation of lower limit value
Violation of upper limit value or limit value on counter
Violation of upper and lower limit values at the same time
"Out of specification"
e.g. input signal too high/low
Error message "Failure detected"
An operating error has occurred. The measured value is no longer valid (e.g.
a channel not displayed in the current group is defective).
"Maintenance required"
Maintenance is required. The measured value is still valid.
Error, measured value not displayed.
Possible causes: Sensor / input error, line break, invalid value, input signal
too high/low
11
Symbol for status signals:
"Device locked"
The setup is locked via a control input or access code. Enter the relevant
access code or unlock the setup using the control input
"Out of specification"
The device is being operated outside its technical specifications (e.g. during
warm-up or cleaning processes).
"Function check"
The device is in Service mode.