Diagnostics and troubleshooting
Universal Data Manager
48
11.10 Simulation
Various functions/signals can be simulated for test purposes here.
NOTICE
Selecting simulation: Simulation of the relays can be found in the main menu under
"Diagnostics -> Simulation". The simulation of the measured values can be found in
the main menu under "Expert -> Diagnostics -> Simulation".
Only the simulated values are recorded during simulation. The simulation is recorded in
the event logbook.
‣
Do not start simulation if measured value recording must not be interrupted!
11.10.1 Test time synchronization / SNTP
Time synchronization (SNTP setting) can be tested in the main menu under
"Diagnostics -
> Simulation -> SNTP"
.
SNTP must be enabled beforehand in the main menu under
"Setup -> Advanced
setup -> System -> Date/time set-up -> SNTP"
.
Note: The test can take some time. A message is provided on the device once the test
has finished.
11.10.2 E-mail test
A test mail can be sent to the selected recipient in the main menu under
"Diagnostics ->
Simulation -> E-mail"
.
At least one e-mail address must be set beforehand. A message is provided on the
device to confirm if the email was sent or not.
11.10.3 Relay test
The relay selected under
"Diagnostics -> Simulation -> Relay x"
can be switched
manually in the main menu.
11.11 Initializing the modem
Initializes the modem connected (to automatically answer calls). The modem must support
the complete AT command syntax.
• Set the baudrate in the main menu under
"Setup -> Advanced setup ->
Communication -> Serial interface"
and select
"RS232"
as the interface type.
• Connect the modem to the RS232 interface of the device. For this purpose only use
the modem cable, which is available as an accessory.
A GSM modem can only be initialized if a SIM card is inserted and the PIN is entered
or the prompt to enter the PIN has been disabled.
11.12 Resetting the measuring device
The device can be reset to the as-delivered state with a PRESET. This function should only
be performed by a service technician.
The function can be found in the main menu under
"Expert -> System -> PRESET"
PRESET is only visible under "Expert" once the service code has been entered.
Procedure for resetting the measuring device
The PRESET returns all parameters to the factory default setup! The internal memory
content is deleted!