![background image](http://html1.mh-extra.com/html/abb/acs880-x04/acs880-x04_firmware-manual_3389539139.webp)
Parameters 139
(Only visible when supply unit control activated by
Shows the control word sent to the supply unit from the INU-
LSU (inverter unit/supply unit) state machine.
This parameter is read-only.
-
0000h…FFFFh
Supply unit control word.
1 = 1
(Only visible when supply unit control activated by
Selects a binary source whose status is transmitted as bit 12
of
to the supply unit.
False
0.
0
True
1.
1
MCW user bit 0
Bit 12 of
(see page
).
2
MCW user bit 1
Bit 13 of
(see page
).
3
MCW user bit 2
Bit 14 of
(see page
).
4
MCW user bit 3
Bit 15 of
(see page
).
5
Source selection (see
). -
(Only visible when supply unit control activated by
Selects a binary source whose status is transmitted as bit 13
of
to the supply unit.
False
0.
0
True
1.
1
MCW user bit 0
Bit 12 of
(see page
).
2
MCW user bit 1
Bit 13 of
(see page
).
3
MCW user bit 2
Bit 14 of
(see page
).
4
MCW user bit 3
Bit 15 of
(see page
).
5
Source selection (see
). -
(Only visible when supply unit control activated by
Selects a binary source whose status is transmitted as bit 14
of
to the supply unit.
False
0.
0
True
1.
1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
ON/OFF
1 = Start charging
0 = Open main contactor (switch power off)
1
OFF 2
0 = Emergency stop (Off2)
2
OFF 3
0 = Emergency stop (Off3)
3
START
1 = Start modulating
0 = Stop modulating
4…6
Reserved
7
RESET
0->1 = Reset an active fault. A fresh start command is required after reset.
8…11
Reserved
12
USER BIT 0 See parameter
13
USER BIT 1 See parameter
14
USER BIT 2 See parameter
15
USER BIT 3 See parameter
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...