104 Application macros
Default control connections for the PID control macro
Fault
P
I
XPOW
External power input
1
+24VI
24 V DC, 2
A
2
GND
XAI
Reference voltage and analog inputs
1
+VREF
10 V DC,
R
L
1…10 kohm
2
-VREF
-10 V DC,
R
L
1…10 kohm
3
AGND
Ground
4
AI1+
Speed reference
0(2)…10 V,
R
in
> 200 kohm
5
AI1-
6
AI2+
Process feedback*
0(4)…20 mA,
R
in
= 100 ohm
7
AI2-
XAO
Analog
outputs
1
AO1
Motor speed rpm
0…20 mA,
R
L
< 500 ohm
2
AGND
3
AO2
Motor current
0…20 mA,
R
L
< 500 ohm
4
AGND
XD2D
Drive-to-drive link
1
B
Master/follower, drive-to-drive or embedded fieldbus
interface connection
2
A
3
BGND
XRO1, XRO2, XRO3
Relay outputs
1
NC
250 V AC / 30 V DC
2 A
2
COM
3
NO
1
NC
250 V AC / 30 V DC
2 A
2
COM
3
NO
1
NC
250 V AC / 30 V DC
2 A
2
COM
3
NO
XD24
Digital interlock
1
DIIL
Digital interlock. By default, not in use.
2
+24VD
+24 V DC 200 mA
3
DICOM
Digital input ground
4
+24VD
+24 V DC 200 mA
5
DIOGND Digital input/output ground
XDIO
Digital input/outputs
1
DIO1
:
2
DIO2
:
XDI
Digital inputs
1
DI1
Stop (0) / Start (1) – Speed control
2
DI2
By default, not in use.
3
DI3
Speed control (0) / Process control (1)
4
DI4
Constant speed 1 (1 = On)
5
DI5
Run enable (1 = On)
6
DI6
Stop (0) / Start (1) – Process control
XSTO
Safe torque off circuits must be closed for the drive to start. See
Hardware manual
of drive.
X12
Safety options connection
X13
Control panel connection
X205
Memory unit connection
*For sensor connection examples, see page
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...