286 Parameters
Configures on-time timer 1.
0000b
0000b…0011b
On-time timer 1 configuration word.
1 = 1
Selects the signal to be monitored by on-time timer 1.
False
Constant 0 (timer disabled).
0
True
Constant 1.
1
RO1
(page
2
). -
Selects the optional warning message for on-time timer 1.
On-time 1
exceeded
. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
0
Clean device
6
Maintain additional
cooling fan
7
Maintain cabinet
fan
.
8
Maintain DC
capacitors
.
9
Maintain motor
bearing
.
10
Displays the actual present value of on-time timer 2.
The timer runs whenever the signal selected by parameter
is on.
When the timer exceeds the limit set by
, bit 1 of
is set to 1. The warning
is also given if
enabled by
The timer can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
-
0…4294967295 s
Actual present value of on-time timer 2.
-
Sets the warning limit for on-time timer 2.
0 s
0…4294967295 s
Warning limit for on-time timer 2.
-
No.
Name/Value
Description
Def
/
FbEq16
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 0 of
) switches to 1 for one second. The warning (if enabled) stays active for at least 10
seconds.
1 = Saturate: When the limit is reached, the counter status (bit 0 of
) switches to 1,
and remains so until
is reset. The warning (if enabled) also stays active until
is reset.
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see
) is given when the limit is reached
2…15
Reserved
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...