Parameters 199
Selects the source of start, stop and direction commands for
external control location 2 (EXT2).
See also parameters
.
Not selected
No start or stop command sources selected.
0
In1 Start
The source of the start and stop commands is selected by
parameter
. The state transitions of the
source bits are interpreted as follows:
1
In1 Start; In2 Dir
is the start
signal; the source selected by
determines the direction. The state transitions of the source
bits are interpreted as follows:
2
In1 Start fwd; In2
Start rev
The source selected by
is the forward
start signal; the source selected by
the reverse start signal. The state transitions of the source bits
are interpreted as follows:
3
In1P Start; In2 Stop The sources of the start and stop commands are selected by
and
.
The state transitions of the source bits are interpreted as
follows:
Note:
The start signal is always edge-triggered with this
setting regardless of parameter
4
No.
Name/Value
Description
Def
/
FbEq16
State of source 1
Command
0?1 (
=
)
Start
0
Stop
State of source 1
State of source 2
)
Command
0
Any
Stop
0?1 (
1 (
0
Start forward
1
Start reverse
State of source 1
State of source 2
)
Command
0
0
Stop
0?1 (
1 (
0
Start forward
0
0?1 (
Start reverse
1
1
Stop
State of source 1
(
)
State of source 2
)
Command
0?1
1
Start
Any
0
Stop
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...