Parameters 303
Defines a stop delay for the motor fan.
The delay timer starts when the control source selected by
parameter
switches off. After the delay, bit 1 of
switches off.
20 min
0…715828 min
Motor fan stop delay.
1 = 1 min
Selects the input for motor fan feedback signal.
0 = Stopped
1 = Running
After the fan is started (bit 1 of
switches on), feedback
is expected within the time set by
.
(
b6)
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
Source selection (see
). -
Defines a feedback delay for the motor fan.
The delay timer starts when bit 1 of
switches on. If no
feedback is received from the fan until the delay elapses, the
action selected by
is taken.
Note:
This delay is only applied at start. If the feedback signal
is lost during run, the action selected by
is taken
immediately.
0 s; 5 s
(
b6)
0…42949673 s
Motor fan start delay.
1 = 1 s
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...