148 Parameters
(Only visible when IGBT supply unit control activated by
)
Version number of the loading package of the supply unit
firmware.
-
10
Configuration of digital inputs and relay outputs.
Displays the electrical status of digital inputs DIIL and
DI6…DI1. The activation/deactivation delays of the inputs (if
any are specified) are ignored. A filtering time can be defined
by parameter
Bits 0…5 reflect the status of DI1…DI6; bit 15 reflects the
status of the DIIL input.
Example:
1000000000010011b =
DIIL, DI5, DI2 and DI1 are on, DI3, DI4 and DI6 are off.
This parameter is read-only.
-
0000h…FFFFh
Status of digital inputs.
1 = 1
Displays the status of digital inputs DIIL and DI6…DI1. This
word is updated only after activation/deactivation delays (if
any are specified). A filtering time can be defined by
parameter
Bits 0…5 reflect the delayed status of DI1…DI6; bit 15 reflects
the delayed status of the DIIL input.
This parameter is read-only.
-
0000h…FFFFh
Delayed status of digital inputs.
1 = 1
The electrical statuses of the digital inputs can be overridden
for eg. testing purposes. A bit in parameter
is provided for each digital input, and its value is applied
whenever the corresponding bit in this parameter is 1.
0000h
0000h…FFFFh
Override selection for digital inputs.
1 = 1
Contains the values that the digital inputs are forced to when
selected by
Bit 0 is the forced value for DI1; bit 15 is the forced value for
the DIIL input.
0000h
0000h…FFFFh
Forced values of digital inputs.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Value
0
1 = Force DI1 to value of bit 0 of parameter
.
1
1 = Force DI2 to value of bit 1 of parameter
.
2
1 = Force DI3 to value of bit 2 of parameter
.
3
1 = Force DI4 to value of bit 3 of parameter
.
4
1 = Force DI5 to value of bit 4 of parameter
.
5
1 = Force DI6 to value of bit 5 of parameter
.
6…14
Reserved
15
1 = Force DIIL to value of bit 15 of parameter
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...