Parameters 369
Parameters
are only effective when the drive is
the master on a D2D (drive-to-drive) link, implemented by
application programming. See parameters
and
, and
Drive
(IEC 61131-3) application programming manual
(3AUA0000127808 [English]).
In the master, parameters
that are monitored for loss of communication.
This parameter selects which followers (out of followers
1…16) are monitored. Each of the selected followers is polled
by the master. If no reply is received, the action specified in
is taken.
The status of communication is shown by
and
-
0000h…FFFFh
Selection of followers for D2D communication supervision (1). 1 = 1
Selects which followers (out of followers 17…32) are
monitored for loss of communication. See parameter
.
-
0000h…FFFFh
Selection of followers for D2D communication supervision (2). 1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Follower 1
1 = Follower 1 is polled by the master.
1
Follower 2
1 = Follower 2 is polled by the master.
…
…
…
15
Follower 16
1 = Follower 16 is polled by the master.
Bit
Name
Description
0
Follower 17
1 = Follower 17 is polled by the master.
1
Follower 18
1 = Follower 18 is polled by the master.
…
…
…
15
Follower 32
1 = Follower 32 is polled by the master.
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...