![background image](http://html1.mh-extra.com/html/abb/acs880-x04/acs880-x04_firmware-manual_3389539365.webp)
Parameters 365
Selects the node address of the drive for master/follower
communication. No two nodes on-line may have the same
address.
Note:
The allowable addresses for the master are 0 and 1.
The allowable addresses for followers are 2…60.
1
1…254
Node address.
Defines the role of the drive on the master/follower or drive-to-
drive link.
Not in use
Master/follower functionality not active.
0
DDCS master
The drive is the master on the master/follower (DDCS) link.
1
DDCS follower
The drive is a follower on the master/follower (DDCS) link.
2
D2D master
The drive is the master on the drive-to-drive (D2D) link.
Note:
This setting is only to be used with D2D communication
implemented by application programming. If you are using the
master/follower functionality (see page
) through the XD2D
instead.
3
D2D follower
The drive is a follower on the drive-to-drive (D2D) link.
Note:
This setting is only to be used with D2D communication
implemented by application programming. If you are using the
master/follower functionality (see page
) through the XD2D
instead.
4
DDCS forcing
The role of the drive on the master/follower (DDCS) link is
defined by parameters
.
5
D2D forcing
The role of the drive on the drive-to-drive (D2D) link is defined
by parameters
and
Note:
This setting is only to be used with D2D communication
implemented by application programming. If you are using the
master/follower functionality (see page
) through the XD2D
instead.
6
Selects the topology of the master/follower link.
Note:
Use the setting
if using the master/follower
functionality (see page
) through the XD2D connector (as
opposed to a fiber optic link).
Ring
The devices are connected in a ring topology. Forwarding of
messages is enabled.
0
Star
The devices are connected in a star topology (for example,
through a branching unit). Forwarding of messages is
disabled.
1
Defines the light intensity of the transmission LED of RDCO
module channel CH2. (This parameter is effective only when
parameter
. FDCO modules have a hardware transmitter current
selector.)
In general, use higher values with longer fiber optic cables.
The maximum setting is applicable to the maximum length of
the fiber optic link. See
Specifications of the fiber optic
).
10
1…15
Light intensity.
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...