358 Parameters
Displays the status of the EFB communication.
This parameter is read-only.
-
0000h…FFFFh
EFB communication status.
1 = 1
Displays a count of valid packets addressed to the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…4294967295
Number of received packets addressed to the drive.
1 = 1
Displays a count of valid packets transmitted by the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…4294967295
Number of transmitted packets.
1 = 1
Displays a count of valid packets addressed to any device on
the bus. During normal operation, this number increases
constantly.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…4294967295
Number of all received packets.
1 = 1
Displays a count of character errors received by the drive. An
increasing count indicates a configuration problem on the bus.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…4294967295
Number of UART errors.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Init failed
1 = EFB initialization failed
1
Addr config err
1 = Node address not allowed by protocol
2
Silent mode
1 = Drive not allowed to transmit
0 = Drive allowed to transmit
3
Autobauding
Reserved
4
Wiring error
1 = Errors detected (A/B wires possibly swapped)
5
Parity error
1 = Error detected: check parameters
6
Baud rate error
1 = Error detected: check parameters
7
No bus activity
1 = 0 bytes received during last 5 seconds
8
No packets
1 = 0 packets (addressed to any device) detected during last 5
seconds
9
Noise or addressing
error
1 = Errors detected (interference, or another device with the
same address on line)
10
Comm loss
1 = 0 packets addressed to the drive received within timeout
(
11
CW/Ref loss
1 = No control word or references received within timeout
(
12
Not active
Reserved
13
Protocol 1
Reserved
14
Protocol 2
Reserved
15
Internal error
Reserved
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...