Parameters 357
Defines the node address of the drive on the fieldbus link.
Values 1…247 are allowable. Two devices with the same
address are not allowed on-line.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
1
0…255
Node address (values 1…247 are allowable).
1 = 1
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
9.6 kbps
9.6 kbit/s.
2
19.2 kbps
19.2 kbit/s.
3
38.4 kbps
38.4 kbit/s.
4
57.6 kbps
57.6 kbit/s.
5
76.8 kbps
76.8 kbit/s.
6
115.2 kbps
115.2 kbit/s.
7
Selects the type of parity bit and the number of stop bits.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
8 NONE 1
Eight data bits, no parity bit, one stop bit.
0
8 NONE 2
Eight data bits, no parity bit, two stop bits.
1
8 EVEN 1
Eight data bits, even parity bit, one stop bit.
2
8 ODD 1
Eight data bits, odd parity bit, one stop bit.
3
Validates any changes in the EFB settings, or activates silent
mode.
Enabled
Normal operation.
0
Refresh settings
Validates any changed EFB configuration settings. Reverts
automatically to
.
1
Silent mode
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the
selection of this parameter.
2
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...