424 Parameters
Number of full days passed since beginning of the year 1980.
This parameter, together with
makes it possible to
set the date and time in the drive via the parameter interface
from a fieldbus or application program. This may be
necessary if the fieldbus protocol does not support time
synchronization.
-
1…59999
Days since beginning of 1980.
1 = 1
Number of full minutes passed since midnight. For example,
the value 860 corresponds to 2:20 pm.
See parameter
0 min
1…1439
Minutes since midnight.
1 = 1
Number of milliseconds passed since last minute.
See parameter
0 ms
0…59999
Number of milliseconds since last minute.
1 = 1
Time source status word.
This parameter is read-only.
-
0000h…FFFFh
Time source status word 1.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Time tick
received
1 = 1st priority tick received: Tick has been received from 1st priority
source (or from
).
1
Aux Time
tick received
1 = 2nd priority tick received: Tick has been received from 2nd priority
source.
2
Tick interval
is too long
1 = Yes: Tick interval too long (accuracy compromised).
3
DDCS
controller
1 = Tick received: Tick has been received from an external controller.
4
Master/
Follower
1 = Tick received: Tick has been received through the master/follower link.
5
Reserved
6
D2D
1 = Tick received: Tick has been received through the drive-to-drive link.
7
FbusA
1 = Tick received: Tick has been received through fieldbus interface A.
8
FbusB
1 = Tick received: Tick has been received through fieldbus interface B.
9
EFB
1 = Tick received: Tick has been received through the embedded fieldbus
interface.
10
Reserved.
11
Panel link
1 = Tick received: Tick has been received from the control panel, or Drive
composer PC tool connected to the control panel.
12
Ethernet tool
link
1 = Tick received: Tick has been received from Drive composer PC tool
through an FENA module.
13
Parameter
setting
1 = Tick received: Tick has been set by parameters
.
14
RTC
1 = RTC time in use: Time and date have been read from the real-time
clock.
15
Drive On-
Time
1 = Drive on-time in use: Time and date are displaying drive on-time.
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...