342 Parameters
49
Communication settings for the control panel port on the drive.
Defines the node ID of the drive. All devices connected to the
network must have a unique node ID.
Note:
For networked drives, it is advisable to reserve ID 1 for
spare/replacement drives.
1
1…32
Node ID.
1 = 1
Defines the transfer rate of the link.
38.4 kbps
38.4 kbit/s.
1
57.6 kbps
57.6 kbit/s.
2
86.4 kbps
86.4 kbit/s.
3
115.2 kbps
115.2 kbit/s.
4
230.4 kbps
230.4 kbit/s.
5
Sets a timeout for control panel (or PC tool) communication. If
a communication break lasts longer than the timeout, the
action specified by parameter
is taken.
10.0 s
0.3 … 3000.0 s
Panel/PC tool communication timeout.
10 = 1 s
Selects how the drive reacts to a control panel (or PC tool)
communication break.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
.
.
No action
No action taken.
0
Fault
. This only occurs if
control is expected from the control panel (it is selected as
source of start/stop/reference in the currently active control
location), or if supervision is forced using parameter
.
1
Last speed
warning and
freezes the speed to the level the drive was operating at. This
only occurs if control is expected from the control panel, or if
supervision is forced using parameter
The speed is determined on the basis of actual speed using
850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
Speed ref safe
Drive generates an
warning and sets
the speed to the speed defined by parameter
(or
is being used). This only occurs if control is expected from the
control panel, or if supervision is forced using parameter
.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...