530 Fault tracing
65B1
Reference source
parametrization
A reference source is
simultaneously connected to
multiple parameters with
different units.
See
(page
).
6681
EFB comm loss
Programmable fault:
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the XD2D
connector on the control unit.
6682
EFB config file
Embedded fieldbus (EFB)
configuration file could not be
read.
Contact your local ABB representative.
6683
EFB invalid
parameterization
Embedded fieldbus (EFB)
parameter settings
inconsistent or not compatible
with selected protocol.
Check the settings in parameter group
.
6684
EFB load fault
Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Contact your local ABB representative.
Version mismatch between
EFB protocol firmware and
drive firmware.
6881
Text data overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
6882
Text 32-bit table
overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
6883
Text 64-bit table
overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
6885
Text file overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
7080
Option module comm
loss
Communication between drive
and an option module is lost.
See
(page
).
7081
Control panel loss
Programmable fault:
Control panel (or PC tool) has
stopped communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
Check the auxiliary code. The code
specifies the I/O port used as follows:
0:
Panel,
1:
Fieldbus interface A,
2:
Fieldbus interface B,
3:
Ethernet,
4:
D2D/EFB port).
7082
Ext I/O comm loss
Programmable fault:
The I/O extension module
types specified by parameters
do not match the detected
configuration.
See
(page
).
7083
Panel reference
conflict
Use of saved control panel
reference in multiple control
modes attempted.
The control panel reference can only be
saved for one reference type at a time.
Consider the possibility of using a copied
reference instead of saved reference
(see the reference selection parameter).
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...