Parameters 281
Sets a custom motor current fault limit.
The drive automatically sets an internal motor current limit
according to the drive hardware. The internal limit is
appropriate in most cases, but this parameter can be used to
set a lower current limit, for example, to protect a permanent
magnet motor from demagnetization.
Note:
The limit defines the maximum peak current of one
phase.
With this parameter at 0.0 A, only the internal limit is in force.
0.00 A
0.00 … 30000.00 A Custom motor current fault limit.
See par.
Selects the stop mode when a non-critical fault occurs.
Coast
The drive coasts to a stop.
0
Emergency ramp
The drive follows the ramp specified for an emergency stop in
parameter
1
Selects how the drive reacts when the communication to an
I/O extension module fails.
No action
No action taken.
0
Warning
The drive generates a warning,
1
Fault
.
2
(Only visible when IGBT supply unit control activated by
)
Selects how the supply unit reacts when an earth fault or
current unbalance is detected.
No action
No action taken.
0
Warning
The supply unit generates a warning,
.
1
Fault
The supply unit trips on a fault,
2
(Only visible when IGBT supply unit control activated by
)
Selects how the supply unit reacts when a supply phase loss
is detected.
No action
No action taken.
0
Fault
The supply unit trips on a fault,
.
1
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...