542 Fault tracing
3E00
Input phase loss
Programmable fault:
Input phase loss detected by
the IGBT bridge.
Check the auxiliary code. Check the
source of the fault corresponding to the
code:
1: Phase A
2: Phase B
4: Phase C
8: Phase cannot be detected
Check the AC fuses.
Check for input power supply imbalance.
3E04
DC link overvoltage
Excessive intermediate circuit
DC voltage.
Check that parameter
is set according to the supply
voltage in use.
3E05
DC link undervoltage
Intermediate circuit DC voltage
is not sufficient because of a
missing supply phase or blown
fuse.
Check supply cabling, fuses and
switchgear.
Check that parameter
is set according to the supply
voltage in use.
3E06
BU DC link difference
Difference in DC voltages
between parallel-connected
supply modules.
Check the DC fuses.
Check the connection to the DC bus.
If the problem persists, contact your local
ABB representative.
3E07
BU voltage difference
Difference in main voltages
between parallel-connected
supply modules.
Check the supply network connections.
Check the AC fuses.
If the problem persists, contact your local
ABB representative.
3E08
LSU charging
DC link voltage is not high
enough after charging.
Check parameter
.
Check supply voltage and fuses.
Check the connection from the relay
output to the charging contactor.
Check that the DC voltage measuring
circuit is working correctly.
4E01
Cooling
Power module temperature is
excessive.
Check ambient temperature. If it exceeds
40 °C (104 °F), ensure that load current
does not exceed derated load capacity.
See appropriate hardware manual
.
Check power module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
power module for dust pick-up. Clean
whenever necessary.
4E02
IGBT temperature
IGBT temperature is
excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against IGBT supply
unit power.
4E03
Excess temperature
Power unit module
temperature is excessive.
See
(page
).
4E04
Excess temperature
difference
High temperature difference
between the IGBTs of different
phases. The amount of
available temperatures
depends on the frame size.
See
).
Code
(hex)
Fault / Aux. code
Cause
What to do
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...