Fault tracing 509
0001 Adapter not found in specified
slot.
Check module location (
or
).
0002 Detected type of interface
module does not match
parameter setting.
Check the module type (
)
against status (
).
0003 Logic version too old.
Contact your local ABB representative.
0004 Software version too old.
Contact your local ABB representative.
0006 Encoder type incompatible with
interface module type.
Check module type (
or
)
against encoder type (
).
0007 Adapter not configured.
Check module location (
or
).
0008 Speed feedback configuration
has changed.
to validate any changes in the
settings.
0009 No encoders configured to
encoder module
Configure the encoder in group
.
000A Non-existing emulation input.
Check input selection (
).
000B Echo not supported by
selected input (for example,
resolver or absolute encoder).
Check input selection (
),
interface module type, and encoder type.
000C Emulation in continuous mode
not supported.
Check input selection (
)
and serial link mode (
)
settings.
A798
Encoder option comm
loss
Encoder feedback not used as
actual feedback, or measured
motor feedback lost (and
parameter
is set to
Check that the encoder is selected as
feedback source in parameter
or
Check that the encoder interface module
is properly seated in its slot.
Check that the encoder interface module
or slot connectors are not damaged. To
pinpoint the problem, try installing the
module into a different slot.
If the module is installed on an FEA-03
extension adapter, check the fiber optic
connections.
Check the auxiliary code (format XXXX
YYYY). “YYYY” indicates the problem
(see actions for each code below).
0001 Failed answer to encoder
configuration message.
Contact your local ABB representative.
0002 Failed answer to adapter
watchdog disable message.
Contact your local ABB representative.
0003 Failed answer to adapter
watchdog enable message.
Contact your local ABB representative.
0004 Failed answer to adapter
configuration message.
Contact your local ABB representative.
0005 Too many failed answers inline
to speed and position
messages.
Contact your local ABB representative.
0006 DDCS driver failed.
Contact your local ABB representative.
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...