Parameters 137
Drive inhibit status word 2. This word specifies the source of
the inhibiting condition that is preventing the drive from
starting. After the condition is removed, the start command
must be cycled. See bit-specific notes.
See also parameter
, bit 1.
This parameter is read-only.
-
0000h…FFFFh
Start inhibit status word 2.
1 = 1
Selects a binary source whose status is transmitted as bit 10
of
False
0.
0
True
1.
1
Above limit
Bit 10 of
(see page
2
Source selection (see
). -
Selects a binary source whose status is transmitted as bit 11
of
False
0.
0
True
1.
1
Ext ctrl loc
Bit 11 of
(see page
).
2
Source selection (see
). -
Selects a binary source whose status is transmitted as bit 12
of
False
0.
0
True
1.
1
Ext run enable
(see page
). 2
Source selection (see
). -
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
Note
0
Follower drive
1 = A follower is preventing the master from starting.
a
1
Application
1 = The application program is preventing the drive from
starting.
b
2
Reserved
3
Encoder feedback 1 = The encoder feedback configuration is preventing the
drive from starting.
a
4
Ref source
parametrization
1 = A reference source parametrization conflict is preventing
the drive from starting. See warning
(page
b
5…15 Reserved
Notes:
a
is still set after the removal of the inhibiting condition,
and edge triggering is selected for the active external control location, a fresh rising-edge
start signal is required. See parameters
,
and
.
b
is still set after the removal of the inhibiting condition, a
fresh rising-edge start signal is required.
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...