Defines whether the start signal for external control location
EXT2 is edge-triggered or level-triggered.
Note:
This parameter is only effective when parameter
is set to
,
, or
.
Edge
The start signal is edge-triggered.
0
Level
The start signal is level-triggered.
1
Selects source 1 for parameter
For the available selections, see parameter
Selects source 2 for parameter
For the available selections, see parameter
Selects source 3 for parameter
For the available selections, see parameter
Selects the way the motor is stopped when the run enable
signal switches off.
The source of the run enable signal is selected by parameter
(
b10)
Coast
Stop by switching off the output semiconductors of the drive.
The motor coasts to a stop.
WARNING!
If a mechanical brake is used, ensure it is
safe to stop the drive by coasting.
0
Ramp
Stop along the active deceleration ramp. See parameter
group
.
1
Torque limit
Stop according to torque limits (parameters
and
). 2
Selects the source of the external run enable signal. If the run
enable signal is switched off, the drive will not start. If already
running, the drive will stop according to the setting of
parameter
.
1 = Run enable signal on.
Note:
The warning that indicates a missing signal can be
suppressed using parameter
.
.
(
b10);
(
b5);
(
b9)
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
FBA A MCW bit 3
Control word bit 3 received through fieldbus interface A.
30
EFB MCW bit 3
Control word bit 3 received through the embedded fieldbus
interface.
32
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...