134 Parameters
Start inhibit status word. This word specifies the source of the
inhibiting condition that is preventing the drive from starting.
After the condition is removed, the start command must be
cycled. See bit-specific notes.
See also parameter
, and
, bit 1.
This parameter is read-only.
-
0000h…FFFFh
Start inhibit status word.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
Note
0
Not ready run
1 = DC voltage is missing or drive has not been parametrized
correctly. Check the parameters in groups
.
a
1
Ctrl location
changed
1 = Control location has changed
a,c
2
SSW inhibit
1 = Control program is keeping itself in inhibited state
a
3
Fault
1 = A fault is active
a,c
4
Lost start enable
1 = Start enable signal missing
a
5
Lost run enable
1 = Run enable signal missing
a
6
FSO inhibit
1 = Operation prevented by FSO-xx safety functions module b
7
STO
1 = Safe torque off active
b
8
Current calibration
ended
1 = Current calibration routine has finished
b,c
9
ID run ended
1 = Motor identification run has finished
b,c
10
Auto phase ended 1 = Autophasing routine has finished
b,c
11
Em Off1
1 = Emergency stop signal (mode Off1)
b
12
Em Off2
1 = Emergency stop signal (mode Off2)
b
13
Em Off3
1 = Emergency stop signal (mode Off3)
b
14
Auto reset inhibit 1 = The autoreset function is inhibiting operation
15
Jogging active
1 = The jogging enable signal is inhibiting operation
b
Notes:
a
is still set after the removal of the inhibiting condition,
and edge triggering is selected for the active external control location, a fresh rising-edge
start signal is required. See parameters
.
b
is still set after the removal of the inhibiting condition, a
fresh rising-edge start signal is required.
c
Informative bit. The inhibiting condition need not be removed by the user.
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...