Parameters 441
Advanced
ID run.
6
Advanced Standstill
ID run.
7
Calculated number of pole pairs in the motor.
This parameter is read-only.
0
0…1000
Number of pole pairs.
1 = 1
Switches the rotation direction of motor. This parameter can
be used if the motor turns in the wrong direction (for example,
because of the wrong phase order in the motor cable), and
correcting the cabling is considered impractical.
Notes:
• Changing this parameter does not affect speed reference
polarities, so positive speed reference will rotate the motor
forward. The phase order selection just ensures that
“forward” is in fact the correct direction.
• After changing this parameter, the sign of encoder
feedback (if any) must be checked. This can be done by
setting parameter
, and comparing the sign of
(or
). If the sign of the measurement is incorrect, the
encoder wiring must be corrected or the sign of
reversed.
• This parameter cannot be changed while the drive is
running.
U V W
Normal.
0
U W V
Reversed rotation direction.
1
Defines the inductance of a custom sine filter, ie. when
parameter
bit 3 is activated.
Note:
For an ABB sine filter (
bit 1),
this parameter is set automatically and should not be
adjusted.
-
0.000 …
100000.000 mH
Inductance of custom sine filter.
1000 = 1 mH
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...