![background image](http://html1.mh-extra.com/html/abb/acs880-x04/acs880-x04_firmware-manual_3389539414.webp)
414 Parameters
Contains hardware-related settings that can be enabled and
disabled by toggling the specific bits.
Notes:
• The installation of the hardware specified by this parameter
may require derating of drive output, or impose other
limitations. Refer to the hardware manual of the drive.
• This parameter cannot be changed while the drive is
running.
-
0000b…0111b
Hardware options configuration word.
1 = 1
(Only visible with a BCU control unit)
Enables/disables router mode of the BCU control unit. When
router mode is active, the PSL2 channels connected to
another BCU (ie. those selected by
) are routed to the power units (converter modules)
connected to this BCU.
See section
Router mode for BCU control unit
(page
Note:
This parameter cannot be changed while the drive is
running.
Off
Router mode inactive.
0
On
Router mode active.
1
). -
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Information
0
EX motor
1 = The driven motor is an Ex motor provided by ABB for potentially
explosive atmospheres. This sets the required minimum switching
frequency for ABB Ex motors.
Note:
For non-ABB Ex motors,
contact your local ABB representative.
1
ABB sine filter
1 = An ABB sine filter is connected to the output of the drive/inverter.
2
High speed mode 1 = Minimum switching frequency limit adaptation to output
frequency active. This setting improves control performance at high
output frequencies (typically above 120 Hz).
3
Custom sine filter
1 = A custom sine filter is connected to the output of the
drive/inverter. See also parameters
,
.
4…15
Reserved
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...