Parameters 157
Defines the minimum for the frequency actually arriving at
frequency input 1 (DIO1 when it is used as a frequency input).
The incoming frequency signal (
)
is scaled into an internal signal (
as follows:
0 Hz
0 … 16000 Hz
Minimum frequency of frequency input 1 (DIO1).
1 = 1 Hz
Defines the maximum for the frequency actually arriving at
frequency input 1 (DIO1 when it is used as a frequency input).
See parameter
.
16000 Hz
0 … 16000 Hz
Maximum frequency for frequency input 1 (DIO1).
1 = 1 Hz
Defines the value that is required to correspond internally to
the minimum input frequency defined by parameter
. See diagram at parameter
0.000
-32768.000 …
32767.000
Value corresponding to minimum of frequency input 1.
1 = 1
Defines the value that is required to correspond internally to
the maximum input frequency defined by parameter
. See diagram at parameter
.
1500.000;
1800.000
(
b0)
-32768.000 …
32767.000
Value corresponding to maximum of frequency input 1.
1 = 1
Displays the value of frequency output 1 after scaling. See
parameter
This parameter is read-only.
-
0 … 16000 Hz
Value of frequency output 1.
1 = 1
Selects a signal to be connected to frequency output 1.
Zero
None.
0
Motor speed used
(page
).
1
Output frequency
).
3
Motor current
(page
4
Motor torque
(page
6
DC voltage
(page
7
Power inu out
(page
8
No.
Name/Value
Description
Def
/
FbEq16
f
in
)
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...