252 Parameters
Determines how constant frequencies are selected, and
whether the rotation direction signal is considered or not when
applying a constant frequency.
0000b
0000b…0011b
Constant frequency configuration word.
1 = 1
When bit 0 of parameter
0 (Separate), selects a source that activates constant
frequency 1.
When bit 0 of parameter
1 (Packed), this parameter and parameters
and
select
three sources whose states activate constant frequencies as
follows:
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Information
0
Constant freq
mode
1 = Packed: 7 constant frequencies are selectable using the three
sources defined by parameters
.
0 = Separate: Constant frequencies 1, 2 and 3 are separately activated
by the sources defined by parameters
and
respectively. In case of conflict, the constant frequency with the smaller
number takes priority.
1
Direction
enable
1 = Start dir: To determine running direction for a constant frequency, the
sign of the constant frequency setting (parameters
) is
multiplied by the direction signal (forward: +1, reverse: -1). This
effectively allows the drive to have 14 (7 forward, 7 reverse) constant
frequencies if all values in
are positive.
WARNING:
If the direction signal is reverse and the active
constant frequency is negative, the drive will run in the forward
direction.
0 = According to Par: The running direction for the constant frequency is
determined by the sign of the constant speed setting (parameters
Source defined
by par.
Source defined
by par.
Source defined
by par.
Constant frequency
active
0
0
0
None
1
0
0
Constant frequency 1
0
1
0
Constant frequency 2
1
1
0
Constant frequency 3
0
0
1
Constant frequency 4
1
0
1
Constant frequency 5
0
1
1
Constant frequency 6
1
1
1
Constant frequency 7
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...