Fieldbus control through the embedded fieldbus interface (EFB) 565
Coils (0xxxx reference set)
Coils are 1-bit read/write values. Control Word bits are exposed with this data type.
The table below summarizes the Modbus coils (0xxxx reference set).
Reference ABB drives profile
Transparent profile
00001
OFF1_CONTROL
Control Word bit 0
00002
OFF2_CONTROL
Control Word bit 1
00003
OFF3_CONTROL
Control Word bit 2
00004
INHIBIT_OPERATION
Control Word bit 3
00005
RAMP_OUT_ZERO
Control Word bit 4
00006
RAMP_HOLD
Control Word bit 5
00007
RAMP_IN_ZERO
Control Word bit 6
00008
RESET
Control Word bit 7
00009
JOGGING_1
Control Word bit 8
00010
JOGGING_2
Control Word bit 9
00011
REMOTE_CMD
Control Word bit 10
00012
EXT_CTRL_LOC
Control Word bit 11
00013
User-defined (0)
Control Word bit 12
00014
User-defined (1)
Control Word bit 13
00015
User-defined (2)
Control Word bit 14
00016
User-defined (3)
Control Word bit 15
00017
Reserved
Control Word bit 16
00018
Reserved
Control Word bit 17
00019
Reserved
Control Word bit 18
00020
Reserved
Control Word bit 19
00021
Reserved
Control Word bit 20
00022
Reserved
Control Word bit 21
00023
Reserved
Control Word bit 22
00024
Reserved
Control Word bit 23
00025
Reserved
Control Word bit 24
00026
Reserved
Control Word bit 25
00027
Reserved
Control Word bit 26
00028
Reserved
Control Word bit 27
00029
Reserved
Control Word bit 28
00030
Reserved
Control Word bit 29
00031
Reserved
Control Word bit 30
00032
Reserved
Control Word bit 31
00033
Reserved
, bit 0
00034
Reserved
, bit 1
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...