292 Parameters
Sets the limit for value counter 2.
With a positive limit, bit 5 of
is set to 1
(and a warning optionally generated) when the counter is
equal or greater than the limit.
With a negative limit, bit 5 of
is set to 1
(and a warning optionally generated) when the counter is
equal or smaller than the limit.
0 = Counter disabled.
0
-2147483008 …
2147483008
Limit for value counter 2.
-
Configures value counter 2.
0000b
0000b…0011b
Value counter 2 configuration word.
1 = 1
Selects the signal to be monitored by value counter 2.
Not selected
None (counter disabled).
0
Motor speed
(see page
).
1
). -
Defines a divisor for value counter 2. The value of the
monitored signal is divided by this value before integration.
1.000
0.001 …
2147483.000
Divisor for value counter 2.
-
Selects the optional warning message for value counter 2.
Value counter 2
exceeded
. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
5
Maintain motor
bearing
.
10
No.
Name/Value
Description
Def
/
FbEq16
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 5 of
) switches to 1 for one second. The warning (if enabled) stays active for at least 10
seconds.
1 = Saturate: When the limit is reached, the counter status (bit 5 of
) switches to 1,
and remains so until
is reset. The warning (if enabled) also stays active until
is reset.
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see
) is given when the limit is reached
2…15
Reserved
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...