144
KHA3000
When the Test Time Expires (61000-3-12)
When the General Judgment is PASS
2
Terminate the test.
Select an item that you want to operate from the test ending menu. For details on the
selection, see "Overview of the Test Ending Menu" on page 146.
3
Compare the set judgment Rsce and Rsce (estimated value) with each
other.
If the judgment Rsce is greater than 33, calculate the Ssc from the judgment Rsce and
rated apparent power of the equipment.
When the judgment Rsce is greater than 33 and equal to or
smaller than the Rsce (estimated value)
4
Calculate the Ssc from the judgment Rsce and rated apparent power of
the equipment.
For details on calculating the Ssc, see "Ssc calculation" on page 144.
When the judgment Rsce is greater than 33 and exceeds the
Rsce (estimated value)
5
Return to "Estimating the Rsce (61000-3-12)" on page 139.
Ssc calculation
Find the Ssc from the rated apparent power of the equipment and judgment Rsce using the
formula for computation in the table on page 140.
In the case of hybrid equipment, each hybrid part is separated for the test. Out of the Rsce for
each separated part, the maximum Rsce is employed as the judgment Rsce. Find the Ssc
from the rated apparent power of the equipment part that is employed as the judgment Rsce
and the judgment Rsce value, using the formula for computation in the table on page 140.
When the General Judgment is FAIL, Increase the Judgment
Rsce
Terminate the test once and restart it. Repeat the following procedure until the general
judgment becomes PASS.
1
Press the F3 key to select Exit.
A dialog box asking whether to save the test results is displayed.
2
Select “No.”
Finish all the exit operations. The screen does not return to the test ending menu. The
next test can be started.
3
Increase the judgment Rsce to a greater value than used the previous
time.
The input range is 33 to 350.
Содержание KHA3000
Страница 20: ...20 KHA3000...
Страница 35: ...Overview This chapter provides an overview of this product and explains the options for the product 1...
Страница 42: ...42 KHA3000 Options...
Страница 49: ...Wiring Measurement Circuits This chapter explains the wiring of measurement circuits and the control circuit 3...
Страница 70: ...70 KHA3000 Connecting Communication Cables...
Страница 71: ...System Setup This chapter explains how to turn on the power and how to set up the system 4...
Страница 91: ...Setting the Harmonic Test This chapter explains how to set the test conditions for the harmonic current test 5...
Страница 120: ...120 KHA3000 Controlling the AC Power Supply...
Страница 182: ...182 KHA3000 Checking the AC Power Supply and Repeatability...
Страница 247: ...Other Measurements This chapter explains basic measurement FFT analyzer and in rush current measurement 11...
Страница 349: ...Maintenance This chapter explains how to clean and inspect this product 14...
Страница 352: ...352 KHA3000 Cleaning and Checking...
Страница 353: ...Specifications This chapter explains the specifications of this product 15...
Страница 390: ...390 KHA3000...
Страница 391: ......