Table 39. IMM error messages (continued)
v
Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v
If an action step is preceded by “(Trained technician only)”, that step must be performed only by a trained
technician.
Memory DIMM
n
Status Scrub failure
detected. (
n
= DIMM
number)
Error
A memory scrub
failure has been
detected.
1.
(Trained technician only) Remove
the affected microprocessor and
check the microprocessor socket
pins for any damaged pins. If a
damage is found, replace the
system board (see Removing the
system board and Installing the
system board).
2.
(Trained technician only) Swap the
affected microprocessor, if there are
more than one microprocessor
installed. If the problem follows the
microprocessor, replace the affected
microprocessor (see Removing a
microprocessor and heat sink and
Installing a microprocessor and heat
sink).
3.
(Trained technician only) Replace
the system board (see Removing the
system board and Installing the
system board).
806f040c-2001ffff
806f040c-2002ffff
806f040c-2003ffff
806f040c-2004ffff
806f040c-2005ffff
806f040c-2006ffff
806f040c-2007ffff
806f040c-2008ffff
806f040c-2009ffff
806f040c-200affff
806f040c-200bffff
806f040c-200cffff
806f040c-200dffff
806f040c-200effff
806f040c-200fffff
806f040c-2010ffff
806f040c-2011ffff
806f040c-2012ffff
806f040c-2013ffff
806f040c-2014ffff
806f040c-2015ffff
806f040c-2016ffff
806f040c-2017ffff
806f040c-2018ffff
Memory DIMM
disabled for DIMM
n
Status. (
n
= DIMM
number)
Info
DIMM disabled.
1.
Make sure the DIMM is installed
correctly (see Memory module
installation).
2.
If the DIMM was disabled because
of a memory fault (memory
uncorrectable error or memory
logging limit reached), follow the
suggested actions for that error
event and restart the server.
3.
Check the IBM support website for
an applicable retain tip or firmware
update that applies to this memory
event. If no memory fault is
recorded in the logs and no DIMM
connector error LED is lit, you can
re-enable the DIMM through the
Setup utility or the Advanced
Settings Utility (ASU).
420
System x3500 M4 Type 7383: Installation and Service Guide
Содержание 7383
Страница 1: ...System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 2: ......
Страница 3: ...System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 8: ...vi System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 42: ...24 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 65: ...Figure 19 Server with sixteen 2 5 inch hard disk drives Chapter 2 Installing optional devices 47 ...
Страница 200: ...182 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 235: ...Figure 53 Server with eight 2 5 inch hard disk drives Chapter 6 Removing and replacing components 217 ...
Страница 236: ...Figure 54 Server with sixteen 2 5 inch hard disk drives 218 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 237: ...Figure 55 Server with twenty four 2 5 inch hard disk drives Chapter 6 Removing and replacing components 219 ...
Страница 360: ...342 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 416: ...398 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 470: ...452 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 479: ...Taiwan Class A compliance statement Notices 461 ...
Страница 480: ...462 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 487: ......
Страница 488: ... Part Number 46W8192 Printed in USA 1P P N 46W8192 ...