Table 11. Light path diagnostics panel LEDs (continued)
v
Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v
If an action step is preceded by "(Trained technician only)," that step must be performed only by a trained
technician.
LED
Description
Action
Memory
When only the Memory LED is
lit, a memory error has occurred.
Note:
Each time you install or remove a DIMM, you must
disconnect the server from the power source; then, wait 10
seconds before restarting the server.If the Configuration LED
is not lit, the system might detect a memory error. Complete
the following steps to correct the problem:
1.
Reseat or swap the DIMMs with lit LEDs.
2.
Check the system-event logs for information about the
error (see “Event logs” on page 144).
3.
Update the server firmware to the latest level (see
“Updating the firmware” on page 101 for more
information).
4.
Replace the failing DIMM (see “Installing a DIMM” on
page 300).
Configuration
When both the Memory and
Configuration LEDs are lit, the
memory configuration is invalid.
If the Memory LED and the Configuration LED are lit, check
the system-event logs for information about the error (see
“Event logs” on page 144).
Power supply
When only the Power supply
LED is lit, a power supply has
failed.
If the CONFIG LED is not lit, the system might detect a
power supply error. Complete the following steps to correct
the problem:
1.
Check the power-supply with an lit yellow LED (see
“Power-supply LEDs” on page 142).
2.
Make sure that the power supplies are seated correctly
and plugged in a good AC outlet.
3.
Remove one of the power supplies to isolate the failed
power supply.
4.
Make sure that both power supplies installed in the
server are of the same voltage.
5.
Replace the failed power supply (see “Removing a
hot-swap power supply” on page 285).
Power Configuration
When both the Power supply
and Configuration LEDs are lit,
the power supply configuration
is invalid.
If the PS LED and the CONFIG LED are lit, the system
issues an invalid power configuration error. Make sure that
both power supplies installed in the server are of the same
rating or wattage.
Over spec
The power supplies are using
more power than their maximum
rating.
If the Over spec LED on the light path diagnostics panel is
lit, complete the following steps in order until the problem
is solved:
1.
Add a second power supply.
2.
Replace the failed power supply.
3.
Remove the optional devices.
140
System x3500 M4 Type 7383: Installation and Service Guide
Содержание 7383
Страница 1: ...System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 2: ......
Страница 3: ...System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 8: ...vi System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 42: ...24 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 65: ...Figure 19 Server with sixteen 2 5 inch hard disk drives Chapter 2 Installing optional devices 47 ...
Страница 200: ...182 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 235: ...Figure 53 Server with eight 2 5 inch hard disk drives Chapter 6 Removing and replacing components 217 ...
Страница 236: ...Figure 54 Server with sixteen 2 5 inch hard disk drives 218 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 237: ...Figure 55 Server with twenty four 2 5 inch hard disk drives Chapter 6 Removing and replacing components 219 ...
Страница 360: ...342 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 416: ...398 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 470: ...452 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 479: ...Taiwan Class A compliance statement Notices 461 ...
Страница 480: ...462 System x3500 M4 Type 7383 Installation and Service Guide ...
Страница 487: ......
Страница 488: ... Part Number 46W8192 Printed in USA 1P P N 46W8192 ...