Troubleshooting ASDA-A3
13-38
13
AL129 Error occurs when writing CANopen PDO to EEPROM
Trigger condition
and cause
An error occurs when saving the current parameter value to ROM.
Checking method
and corrective action
When PDO is receiving or sending, check if the error occurs because the specified
object is written to EEPROM.
How to clear the
alarm?
NMT: reset node or 0x6040 fault reset.
AL130 Accessing address of EEPROM is out of range when using CANopen PDO
Trigger condition
and cause
The quantity of the data in the ROM is greater than the allowable space specified
by the firmware. It is probably because the firmware has been updated, but the
data in the ROM was stored by the old version of the firmware.
Checking method
and corrective action
Check if the addressing in EEPROM exceeds the range for the specified object
during PDO receiving or sending.
How to clear the
alarm?
NMT: reset node or 0x6040 fault reset.
AL131 CRC of EEPROM calculation error occurs when using CANopen PDO
Trigger condition
and cause
The data in ROM is damaged. All CAN objects are automatically restored to default
values.
Checking method
and corrective action
Check if the specified object causes a CRC calculation error in EEPROM during
PDO receiving or sending. Usually, this alarm is caused by an error in DSP.
How to clear the
alarm?
NMT: reset node or 0x6040 fault reset.
AL132 Parameter is write-prohibited when using CANopen PDO
Trigger condition
and cause
When using CAN object to write data to the parameter, the parameter is currently
write-prohibited.
Checking method
and corrective action
Refer to the specified parameter description to write data to the parameter.
How to clear the
alarm?
NMT: reset node or 0x6040 fault reset.
AL180 CANopen heartbeat or NodeGuarding error
Trigger condition
and cause
CANopen communication is cut off resulting in heartbeat or NodeGuarding error.
Checking method
and corrective action
1.
Check if the CANopen communication is normal.
2.
Check if the wiring is correctly connected.
How to clear the
alarm?
NMT: reset node or 0x6040 fault reset.
Содержание ASDA-A3 Series
Страница 15: ... This page is intentionally left blank ...
Страница 89: ...Wiring ASDA A3 3 38 3 Pin assignment for the CN1 quick connector J2 and J1 ...
Страница 91: ...Wiring ASDA A3 3 40 3 Wiring for CN1 quick connector and installation Installation ...
Страница 296: ...ASDA A3 Motion Control 7 99 7 Figure 7 3 4 6 ASDA Soft Speed fitting setting interface for creating E Cam table ...
Страница 320: ...ASDA A3 Motion Control 7 123 7 Figure 7 3 7 14 ASDA Soft rotary shear intermittent printing machine setting interface ...
Страница 373: ...Motion Control ASDA A3 7 176 7 This page is intentionally left blank ...
Страница 605: ...Parameters ASDA A3 8 232 8 This page is intentionally left blank ...
Страница 623: ...MODBUS Communication ASDA A3 9 18 9 This page is intentionally left blank ...
Страница 645: ...Absolute System ASDA A3 10 22 10 This page is intentionally left blank ...
Страница 661: ...Linear Motor ASDA A3 11 16 11 This page is intentionally left blank ...
Страница 793: ...Troubleshooting ASDA A3 13 48 13 This page is intentionally left blank ...
Страница 819: ...Specifications ASDA A3 A 26 A This page is intentionally left blank ...
Страница 841: ...Accessories ASDA A3 B 22 B This page is intentionally left blank ...