Troubleshooting by Error Code
SiME332106E
242
Part 6 Service Diagnosis
Reference
Reference
Reference
Troubleshooting
CHECK 2
Refer to page 272.
CHECK 3
Refer to page 273.
CHECK 7
Refer to page 279.
Replace the thermistor
(R3T).
NO
Replace the outdoor unit
main PCB (A1P).
YES
YES
Are the
characteristics of the
suction pipe thermistor
normal?
NO
Are the
characteristics of the
low pressure sensor
normal?
Replace the low pressure
sensor (S1NPL).
Correct the abnormally low
pressure.
Correct the insufficient low
refrigerant condition.
Correct the superheat
operation.
NO
YES
Is refrigerant shortage detected
as a cause of abnormally
low pressure?
NO
YES
YES
YES
Is refrigerant
insufficient?
NO
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
CHECK 2
Is another cause detected as a
cause of abnormally low
pressure?
CHECK 2
Is refrigerant shortage detected
as a cause of superheat
operation?
CHECK 3
CHECK 7
Is another cause detected
as a cause of superheat
operation?
CHECK 3
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...