Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
89
1.1.4 BRC4M Series
Setting
To set the field settings, you have to change:
Mode No.
First code No.
Second code No.
To change the field settings, proceed as follows:
1. Hold down the
INSPECTION
button for at least 4 seconds during normal mode to enter the
field setting mode.
2. Press the
MODE
button to select the desired mode No.
3. Press the
FAN
or
BACK LIGHT
button to select the first code No.
4. Press the
TEMP
button to select the second code No.
5. Press the
RESERVE
button to set the present settings.
6. Press the
INSPECTION
button to return to the normal mode.
Mode No.
5
2
1,6
4
3
First code
No.
Second
code No.