SiME332106E
Capacity Range
Part 1 General Information
11
3. Capacity Range
3.1 Connection Ratio
3.2 Outdoor Unit Combinations
Type
Min. connection ratio
Max. connection ratio
Single outdoor units
50%
130%
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Model
RXYMQ4AVMK
RXYMQ4AYFK
RXYMQ5AYFK
RXYMQ6AYFK
kW
11.3
14.1
16.0
HP
4
5
6
Capacity index
100
125
150
Total capacity index
of connectable
indoor units
Combination (%)
50%
50
62.5
75
100%
100
125
150
130%
130
162.5
195
Maximum number of connectable indoor units
6
8
9