SiME332106E
Main/Sub Setting
Part 3 Remote Controller
35
2. When 2 remote controllers are being used, it is not possible to change the setting from Main
to Sub if one of the remote controllers is already set as Main.
3.2 Wired Remote Controller (BRC1H81 Series)
When using 1 remote controller
Once the controller is powered, it will automatically start up:
If it is the first and only controller that is connected to the indoor unit, it will automatically get
designated as master controller.
When using 2 remote controller
For a second controller to get designated as slave controller, manual action is required.
1. Connect a second controller.
Result:
It will start up automatically.
2. Wait for a
U5
or
U8
error to appear on the screen.
3. When the
U5
or
U8
error appears, press and keep it pressed until "2" appears on the
screen.
a
b
c
a
c
b
Outdoor unit
Indoor unit
Master remote controller
a
b
c
d
a
c
d
b
Outdoor unit
Indoor unit
Master remote controller
Slave remote controller
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...