SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
215
5.36 Thermistor Abnormality
Applicable
Models
All outdoor unit models
Error Code
H9, J3, J5, J6, J7, J8, J9
Method of Error
Detection
Detect according to temperature detected with individual thermistors.
Error Decision
Conditions
When the system is in operation and the thermistor causes wiring disconnection or short circuit
in it.
Supposed
Causes
Defective connection of thermistor
Defective thermistor
Defective outdoor unit main PCB
Troubleshooting
Thermistor is
connected to the
connector.
Replace the outdoor unit main
PCB (A1P).
Connect the connector and turn
ON again.
NO
NO
Replace the thermistor (
1).
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
CHECK 11
Resistance is
normal when
measured after
disconnecting the
thermistor from the
outdoor unit
main PCB.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...