SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
239
5.51 Field Setting after Replacing Outdoor Unit Main PCB
Abnormality or Combination of PCB Abnormality
Applicable
Models
All outdoor unit models
Error Code
PJ
Method of Error
Detection
This error is detected according to communications with the outdoor unit main PCB
(RXYMQ4AVMK) or inverter PCB (RXYMQ4-6AYFK).
Error Decision
Conditions
Make judgment according to communication data on whether or not the type of the outdoor unit
main PCB (RXYMQ4AVMK) or inverter PCB (RXYMQ4-6AYFK) is correct.
Supposed
Causes
Mismatching of type of PCB
Improper (or no) field setting after replacing outdoor unit main PCB
Troubleshooting
RXYMQ4AVMK
RXYMQ4-6AYFK
Has the
DIP switch setting
been made properly to
replace the outdoor unit
main PCB?
YES
NO
YES
NO
Replace with a correct
outdoor unit main PCB
(A1P).
Properly make DIP switch
setting.
(After completion of setting,
reset the power supply.)
Replace the outdoor unit
main PCB (A1P).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Does the
outdoor unit main PCB
part No. match that of the
spare parts list?
Has the
DIP switch setting
been made properly to
replace the outdoor unit
main PCB?
YES
YES
NO
NO
YES
NO
Replace with a correct
inverter PCB (A3P).
Replace with a correct fan
PCB (A4P).
Properly make DIP switch
setting.
(After completion of setting,
reset the power supply.)
Replace the outdoor unit
main PCB (A1P).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Does the
inverter PCB part
No. match that of the
spare parts list?
Does the fan
PCB part No. match that
of the spare parts list?
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...