Protection Control
SiME332106E
60
Part 4 Functions and Control
6.2 Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
Cooling
Because of common low pressure, the following control is performed in the system.
Heating
The following control is performed in the system.
6.3 Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against an error or transient increase of discharge pipe temperature.
Normal control
Pe < 0.35 MPa
Low pressure standby
Reduce compressor capacity step
Pe < 0.07 MPa
Pe > 0.40 MPa
When occurring 3 times within 60
minutes, the error code
E4
is output.
Pe: Low pressure sensor detection
value for master unit.
Normal operation
Pe < 0.17 MPa
Low pressure standby
Reduce compressor capacity step
Pe < 0.07 MPa
Pe > 0.23 MPa
When occurring 3 times within 60
minutes, the error code
E4
is output.
Normal control
Discharge pipe temperature > 135°C
Discharge pipe
temperature < 95°C
Discharge pipe
temperature > 108°C
Reduce compressor capacity step
Discharge pipe temperature standby
When occurring 3 times within 100
minutes, the error code
F3
is output.
(Sub code - 01)
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...