Troubleshooting by Error Code
Part 6 Service Diagnosis
183
Troubleshooting
Properly connect the connector.
NO
YES
Is the X70A
connector on the indoor
unit PCB properly
connected?
Properly connect the connector.
NO
YES
Is the X12A
connector on the auto grille
control PCB properly
connected?
Replace the harness.
YES
Is the harness
disconnected?
NO
YES
NO
Remove the external factor.
YES
Is there any
external factor such as
noise?
Check the indoor unit PCB and
the auto grille control PCB.
NO
Is
"Auto grille
elevation operation"
displayed in the remote
controller menu?
Normal.
YES
Check the indoor unit PCB and
the auto grille control PCB.
NO
Can
the target unit be
selected?
Turn OFF the power once and turn
ON again. Then, start grille
operation with remote controller.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...