SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
213
Note(s)
Reference
Troubleshooting
OL (Q1M) activating temperature: 125°C
OL (Q1M) recovery temperature: 110°C
1. RXYMQ4AVMK: X3A
RXYMQ4-6AYFK: X5A
CHECK 11
Refer to page 281.
Caution
YES
NG
NO
OK
YES
NO
Disconnect the connector
(
1)
from the PCB.
Disconnect the 2 terminals of
the OL (Q1M).
Resistance
Resistance
Nearly 0
Nearly 0
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the outdoor unit
main PCB (A1P).
Discharge pipe
thermistor disconnected?
CHECK 11
Check the discharge pipe
thermistor.
Replace the OL (Q1M).
Replace the OL harness.
Connect the connector (
1)
properly.
Is the OL connector
(
1) properly connected?
Check the
resistance between
the 2 terminals on the
connector
(
1).
Check the
resistance between the
2 terminals of the OL
(Q1M).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...