SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
207
Reference
Reference
Troubleshooting
CHECK 3
Refer to page 273.
CHECK 11
Refer to page 281.
NO
Is the
temperature
checked by the
Service Checker same as
the measurement of the
temperature?
NO
Replace the discharge pipe
thermistor (R21T).
Replace the outdoor unit main
PCB (A1P).
YES
YES
Service Checker
Connect the Service Checker, and then compare the
discharge pipe temperature measured by the Service
Checker and the measurement of discharge pipe
surface temperature.
Connect the Service Checker.
Reset the system operation,
and then restart it.
Are
the characteristics
of the discharge pipe
thermistor normal?
CHECK 11
• Thermistor is normal, and temperature detection with
the outdoor unit main PCB is also normal.
• The discharge pipe temperature has really become
high.
CHECK 3
Eliminate the causes of superheat operation.
NO
Open the stop valve.
YES
Is the stop valve open?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...