Outline of Control (Indoor Unit)
SiME332106E
72
Part 4 Functions and Control
8.3 Automatic Airflow Rate Control
The automatic airflow rate control (Five steps from H to L) is based on the difference between
control target temperature and set temperature.
1. LL airflow for FXFSQ-AR
Conditions
When airflow rate is set
Automatic airflow rate
Cooling
Thermostat ON
Set
The fan tap is determined
by the difference between control target
temperature and set temperature.
Thermostat OFF
Set (
1)
The fan keeps rotating at
the speed as just before
the thermostat off (
1)
Heating
Thermostat ON
Set
The fan tap is determined
by the difference between control target
temperature and set temperature.
Thermostat OFF
LL
LL
Program dry
Thermostat ON
L
L
Thermostat OFF
OFF
OFF
Fan
Set
M
Stop
OFF
OFF
H
HM
M
ML
L
Fan tap
Large
Difference between control target
Small
temperature and set temperature
<Change in airflow rate under
automatic airflow rate control>
Except for FXFSQ-AR,
HM and ML taps appear
only during the auto
airflow rate control
operation.
(For FXFSQ-AR,
HM and ML taps can be
manually set with remote
controller.)
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...