Troubleshooting by Error Code
SiME332106E
184
Part 6 Service Diagnosis
Note(s)
Reference
5.16 Thermistor Abnormality
Applicable
Models
All indoor unit models
Error Code
C4, C5, C9
Method of Error
Detection
The error is determined by the temperature detected by the thermistor.
Error Decision
Conditions
The thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Defective thermistor
Defective indoor unit PCB
Disconnection of connector
Troubleshooting
Error code and thermistor
CHECK 11
Refer to page 281.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Remove the thermistor from
the indoor unit PCB. Then,
insert the connector again.
Remove the thermistor from
the indoor unit PCB, and then
measure the resistance of the
thermistor using a multimeter.
CHECK 11
Normal (The error is caused by
defective contact.)
YES
NO
Replace the indoor unit
control PCB (A1P).
YES
Replace the thermistor.
NO
Does the unit
operate normally?
Normal?
Error Code
Thermistor
Electric Symbol
C4
Indoor heat exchanger liquid pipe thermistor
R2T
C5
Indoor heat exchanger gas pipe thermistor
R3T
C9
Suction air thermistor
R1T
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...