Troubleshooting by Error Code
SiME332106E
160
Part 6 Service Diagnosis
5.3 External Protection Device Abnormality
Applicable
Models
All indoor unit models
Error Code
A0
Method of Error
Detection
Detects open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
An open circuit occurs between external input terminals with the remote controller set for
external ON/OFF input.
Supposed
Causes
Activation of external protection device
Improper field setting
Defective indoor unit PCB
Troubleshooting
Activation of external
protection device.
External
protection device is
connected to terminals T1 and
T2 of the indoor unit
terminal block.
Replace the indoor unit
control PCB (A1P).
YES
Change the second code
No. to
01
or
02
.
External
ON/OFF input (mode
No. 12, first code No. 1) has
been set to external protection
device input (second code
No. 03) by remote
controller.
YES
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the setting state of the
ON/OFF input from outside by remote
controller.
NO
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...